Addressable Manual Call Points

Fire Alarm (FA) System

Product PDF
Specifications
Model QA19 QA0817
Purpose Signal will directly sent to panel
System Connected Control panel zone
Input Source Zone signal
Output Contacts/Load N/A
EOL Resistor 10kΩ
Address Coding Binary
Operating Voltage 16 ~ 32V DC
Alarm Current 6mA
Quiescent Current 650 ~ 850μA
Ambient Temperature 0°C ~ +50°C
Material Fire-proof plastic
Color Red
Dimensions(mm) 140(Dia.) x 45(H) 87.5(H) x 87.5(W) x 54(D)
Remarks Protection Cover is optional